The MarsLab-61850 is equipped for performing a full range of test/calibration works of measuring equipment in both conventional and digital (IEC 61850-9-2) substations.
Electronic current transformers with IEC 61850-9-2 digital outputs rated at up to 5 kA | |
Electronic voltage transformers with IEC 61850-9-2 digital outputs rated at up to 500/√3 kV | |
Conventional current and voltage instrument transformers (accuracy class 0.2) | |
Merging Units (accuracy class 0.1) | |
Electrical energy meters with either digital (IEC 61850-9-2) or conventional inputs (accuracy class 0.2S) | |
Phasor Measurement Units (PMU) of accuracy class 0.1 | |
Protection and control equipment with IEC 61850-9-2 inputs (accuracy class 0.2) | |
Power Quality Analyzers |
The mobile laboratory was designed to be used by metrological inspection services: to test, maintain and repair to some extent measuring equipment installed at both conventional and digital substations and to perform their regular calibration and certification.
Accuracy class: 0.05
Rated currents:
TTIP 100/5(1): 5; 10; 15; 20; 25; 30; 40; 50; 60; 75; 80; 100 A
TTIP 5000/5(1): 150; 200; 250; 300; 400; 500; 600; 750; 800; 1000; 1200; 1500; 2000; 3000; 4000; 5000 A
Accuracy classes: 0.05, 0.1
Rated voltages:
6/√3; 6; 10/√3; 15; 35/√3; 35; 110/√3; 220/√3; 330/√3; 500/√3 kV
Other values of rated voltages are available on request.
Accuracy classes: 0.02; 0.05
Basic accuracy charcteristics
Transformer type |
Measurement error |
|
Ratio |
Phase |
|
Analogue |
0.002 % |
0.1 min |
Digital |
0.015 % |
1 min |
As part of the reference setup MarsTest-61850, Energomonitor-61850 provides for accuracy testing of Merging Units, conventional electrical energy meters, PQ analyzers, protection and control systems.
Basic errors of setting: ±0.03 %.
Synchronization error (1 PPS): ±2•10–6 Hz
As part of the reference setup MarsTest-61850, the calibrator provides for accuracy testing of digital meters, PQ analyzers, protection and control systems with IEC 61850-9-2 digital outputs.