In response to the growing need for the equipment capable of testing current or voltage LPITs (Low power instrument transformers), Mars-Energo offers test sets, all based on a duel-channel reference comparator of voltage MarsComp K-1000 especially designed for this purpose.
Our test sets range from a budget one (no PC control) to the automated setups complete with a PC-controlled source of current or voltage test signals that provide fully automatic control of test process from a PC.
If not only LPITs but also conventional transformers would need to be calibrated with one and the same test system, any of these sets could be complemented with a “traditional” comparator Energomonitor 3.1KM (accuracy class 0.05) or Energomonitor 3.3T1 (accuracy class 0.1).
The test set is equipped with a source of test current IT5000 that does not support a PC control function. Therefore, the set allows LPITS to be tested just in the manual mode.
The IT5000 current source and the reference transformers of TTIP series produced by Mars-Energo can be replaced with either a suitable customer’s current source or customer’s reference transformers with appropriate characteristics and accuracy.
Basic characteristics of current LPITs under test:
Applicable standards | IEC 60044-8, IEC 61869-10 |
Primary current range | 0.05 A to 6000 A |
Metering accuracy | IEC class 0.2S (or less accurate) |
Low-energy analog outputs | 0.5 mV to 9 V |
This set will provide max ranging and functionality (available at Mars-Energo) with respect to testing of current LPITs. The source of test current IT5000A is PC-controlled, that is why testing can be performed in fully automatic mode.
The reference transformers of TTIP series produced by Mars-Energo can be replaced by customer’s reference transformers with suitable characteristics and of appropriate accuracy.
Basic characteristics of current LPITs under test:
Applicable standards | IEC 60044-8, IEC 61869-10 |
Primary current range | 0.05 A to 6000 A |
Metering accuracy | IEC class 0.2S (or less accurate) |
Low-energy analog outputs | 0.5 mV to 9 V |
Electronic turns ratio | user selectable |
To test conventional CTs, set 1 or set 2 for testing current LPITs can be complemented with the units listed below. The burden box (produced by other manufacturer) can be replaced by a customer’s burden box with suitable characteristics.
Basic characteristics of conventional CTs under test:
Applicable standards | IEC 61869-2 |
Primary current range | 0.05 A to 6000 A |
Metering accuracy | Class 0.2S (or less accurate) with the comparator EM 3.1KM Class 0.5S (or less accurate) with the comparator EM 3.3T1 |
High-energy analog outputs | 1 A, 5 A |
This set will provide max ranging and functionality (available at Mars-Energo) with respect to the testing of voltage LPITs. Depending on the desired range, the set may include one of the test voltage sources (both PC-controlled): up to 35 kV, or up to 110/√3 kV.
The test voltage source up to 35 kV consists of a test transformer (produced by other manufacturer, replaceable by a customer’s one) and a laboratory-type variable-ratio transformer LATR-IT5000A (controlled from a PC).
The HV module for testing VTs 110/√3 kV is produced by other manufacturer, and thus it can be replaced by a customer’s one.
The primary voltage range can be expanded up to 330/√3 kV (with use of the Mars-Energo’s reference voltage transducer CHVT-330 up to 330/√3 kV), however the weight of the corresponding HV module adds up to
1450 kg.
Basic characteristics of voltage LPITs under test:
Applicable standards | IEC 60044-7, IEC 61869-11 |
Primary voltage range | single-phase; up to 35 kV; up to 110/√3 kV (up to 330/√3 kV) |
Metering accuracy | Accuracy class 0.5 (or less accurate) |
Low-energy analog outputs | 0.5 mV to 9 V |
Electronic turns ratio | user selectable |
To test conventional VTs, a set for testing voltage LPITs can be complemented with the units listed below. The burden box (produced by other manufacturer) can be replaced by a customer’s burden box with suitable characteristics.
Basic characteristics of conventional VTs under test:
Applicable standards | IEC61869-3 |
Primary voltage range | up to 35 kV, up to 110√3 kV |
Metering accuracy | Class 0.2 (or less accurate) with the comparator EM 3.1KM Class 0.5 (or less accurate) with the comparator EM 3.3T1 (if the reference device has accuracy class 0.05 or better) |
Analog outputs | 100, 100/√3, 110, 110/√3 V |