Sets for testing LPITs

In response to the growing need for the equipment capable of testing current or voltage LPITs (Low power instrument transformers), Mars-Energo offers test sets, all based on a duel-channel reference comparator of voltage MarsComp K-1000 especially designed for this purpose.

Our test sets range from a budget one (no PC control) to the automated setups complete with a PC-controlled source of current or voltage test signals that provide fully automatic control of test process from a PC.

If not only LPITs but also conventional transformers would need to be calibrated with one and the same test system, any of these sets could be complemented with a “traditional” comparator Energomonitor 3.1KM (accuracy class 0.05) or Energomonitor 3.3T1 (accuracy class 0.1).

1. Budget set for testing current LPITs

The test set is equipped with a source of test current IT5000 that does not support a PC control function. Therefore, the set allows LPITS to be tested just in the manual mode.

The IT5000 current source and the reference transformers of TTIP series produced by Mars-Energo can be replaced with either a suitable customer’s current source or customer’s reference transformers with appropriate characteristics and accuracy.

Basic characteristics of current LPITs under test:

Applicable standards IEC 60044-8, IEC 61869-10
Primary current range 0.05 A to 6000 A
Metering accuracy IEC class 0.2S (or less accurate)
Low-energy analog outputs 0.5 mV to 9 V

2. Automated set for testing current LPITs

This set will provide max ranging and functionality (available at Mars-Energo) with respect to testing of current LPITs. The source of test current IT5000A is PC-controlled, that is why testing can be performed in fully automatic mode.

The reference transformers of TTIP series produced by Mars-Energo can be replaced by customer’s reference transformers with suitable characteristics and of appropriate accuracy.

Basic characteristics of current LPITs under test:

Applicable standards IEC 60044-8, IEC 61869-10
Primary current range 0.05 A to 6000 A
Metering accuracy IEC class 0.2S (or less accurate)
Low-energy analog outputs 0.5 mV to 9 V
Electronic turns ratio user selectable

3. Multi-purpose set for testing current transformers (LPITs + Conventional CTs)

To test conventional CTs, set 1 or set 2 for testing current LPITs can be complemented with the units listed below. The burden box (produced by other manufacturer) can be replaced by a customer’s burden box with suitable characteristics.

Basic characteristics of conventional CTs under test:

Applicable standards IEC 61869-2
Primary current range 0.05 A to 6000 A
Metering accuracy Class 0.2S (or less accurate) with the comparator EM 3.1KM
Class 0.5S (or less accurate) with the comparator EM 3.3T1
High-energy analog outputs 1 A, 5 A

4. Automated set for testing voltage LPITs

This set will provide max ranging and functionality (available at Mars-Energo) with respect to the testing of voltage LPITs. Depending on the desired range, the set may include one of the test voltage sources (both PC-controlled): up to 35 kV, or up to 110/√3 kV.

The test voltage source up to 35 kV consists of a test transformer (produced by other manufacturer, replaceable by a customer’s one) and a laboratory-type variable-ratio transformer LATR-IT5000A (controlled from a PC).

The HV module for testing VTs 110/√3 kV is produced by other manufacturer, and thus it can be replaced by a customer’s one.

The primary voltage range can be expanded up to 330/√3 kV (with use of the Mars-Energo’s reference voltage transducer CHVT-330 up to 330/√3 kV), however the weight of the corresponding HV module adds up to
1450 kg.

Basic characteristics of voltage LPITs under test:

Applicable standards IEC 60044-7, IEC 61869-11
Primary voltage range single-phase; up to 35 kV; up to 110/√3 kV (up to 330/√3 kV)
Metering accuracy Accuracy class 0.5 (or less accurate)
Low-energy analog outputs 0.5 mV to 9 V
Electronic turns ratio user selectable

5. Multi-purpose set for testing voltage transformers
(LPITs + Conventional VTs)

To test conventional VTs, a set for testing voltage LPITs can be complemented with the units listed below. The burden box (produced by other manufacturer) can be replaced by a customer’s burden box with suitable characteristics.

Basic characteristics of conventional VTs under test:

Applicable standards IEC61869-3
Primary voltage range up to 35 kV, up to 110√3 kV
Metering accuracy Class 0.2 (or less accurate) with the comparator EM 3.1KM
Class 0.5 (or less accurate) with the comparator EM 3.3T1 (if the reference device has accuracy class 0.05 or better)
Analog outputs 100, 100/√3, 110, 110/√3 V